Supplying you with customized 600/1000v lszh sheathed, screened (3c+3e), it is one of the reliable 600/1000v lszh sheathed, screened (3c+3e) manufacturers and suppliers, welcome to wholesale our products at good price from our factory.
600/1000V LSZH Sheathed, Screened (3C+3E)
Application: |
The cables are designed specifically to suit the broad spectrum of requirements of Variable Speed Drives and also include features for reducing the transmission of electromagnetic interference. |
Standard: |
Basic design to IEC 60502-1 |
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test) |
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) |
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free |
IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission |
IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
minimum Smoke Emission |
IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases |
NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard.
VOLTAGE RATING
600/1000V
CABLE CONSTRUCTION
Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.
Insulation: Extruded cross-linked XLPE compound.
Screen: Copper Tape
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
COLOUR CODE
Insulation Colour: Red, Yellow, Blue, Green/Yellow (x3)
Outer sheath: Black or as order
Physical AND THERMAL PROPERTIES
Temperature range during operation: Max.90°C for XLPE
250°C in short-circuit for 5s max.
Minimum bending radius: 10 x Overall Diameter
CONSTRUCTION PARAMETERS
Conductor |
||||||
No. of Core X Cross Section |
No./Nominal Diameter of Strands |
Combined Earth Size |
Nominal Insulation Thickness |
Nominal Sheath Thickness |
Nominal Overall Diameter |
Approx. Weight |
mm² |
No./mm |
mm² |
mm |
mm |
mm |
kg/km |
3x1.5 |
7/0.53 |
4.5(3x1.5) |
0.7 |
1.8 |
13.6 |
325 |
3x2.5 |
7/0.67 |
4.5(3x1.5) |
0.7 |
1.8 |
14.8 |
380 |
3x4 |
7/0.85 |
4.5(3x1.5) |
0.7 |
1.8 |
15.8 |
440 |
3x6 |
7/1.04 |
7.5(3x2.5) |
0.7 |
1.8 |
16.9 |
550 |
3x10 |
7/1.35 |
12(3x4) |
0.7 |
1.8 |
18.6 |
750 |
3x16 |
7/1.70 |
18(3x6) |
0.7 |
1.8 |
20.8 |
1000 |
3x25 |
7/2.14 |
30(3x10) |
0.9 |
1.8 |
24.0 |
1470 |
3x35 |
7/2.52 |
30(3x10) |
0.9 |
1.8 |
25.6 |
1890 |
3x50 |
19/1.78 |
30(3x10) |
1.0 |
1.9 |
31.1 |
2300 |
3x70 |
19/2.14 |
48(3x16) |
1.1 |
2.0 |
34.6 |
3200 |
3x95 |
19/2.52 |
48(3x16) |
1.1 |
2.2 |
39.3 |
4200 |
3x120 |
37/2.03 |
75(3x25) |
1.2 |
2.3 |
44.0 |
5400 |
3x150 |
37/2.25 |
75(3x25) |
1.4 |
2.5 |
49.0 |
6400 |
3x185 |
37/2.52 |
105(3x35) |
1.6 |
2.6 |
54.0 |
7900 |
3x240 |
61/2.25 |
150(3x50) |
1.7 |
2.8 |
61.0 |
10200 |
3x300 |
61/2.52 |
150(3x50) |
1.8 |
3.0 |
67.0 |
12300 |
Electrical PROPERTIES
Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C
Current-Carrying Capacities (Amp)
Conductor cross- sectional area |
Reference method 4 (enclosed in conduit in thermally insulating wall etc) |
Reference method 3 (enclosed in conduit on a wall or in trunking etc) |
Reference method 1 (clipped direct) |
Reference method 11 (on a perforated cable tray, horizontal or vertical) |
Reference method 12 (free air) |
||||||
Horizontal flat spaced |
Vertical flat spaced |
Trefoil |
|||||||||
2 cables, single- phase a.c. or d.c. |
3 or 4 cables, 3-phase a.c. |
2 cables, single- phase a.c. or d.c |
3 or 4 cables, 3-phase a.c. |
2 cables, single- phase a.c. or d.c. flat and touching |
3 or 4 cables, 3-phase a.c. flat and touching or trefoil |
2 cables, single- phase a.c. or d.c. or flat and touching |
3 or 4 cables, 3-phase a.c. flat and touching or trefoil |
2 cables, single- phase a.c. or d.c. or 3 c ables three phase |
2 cables, single- phase a.c. or d.c. or 3 cables three phase |
3 cables, trefoil 3-phase a.c. |
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
mm² |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
1.5 |
18 |
17 |
22 |
19 |
25 |
23 |
- |
- |
- |
- |
- |
2.5 |
24 |
23 |
30 |
26 |
34 |
31 |
- |
- |
- |
- |
- |
4 |
33 |
30 |
40 |
35 |
46 |
41 |
- |
- |
- |
- |
- |
6 |
43 |
39 |
51 |
45 |
59 |
54 |
- |
- |
- |
- |
- |
10 |
58 |
53 |
71 |
63 |
81 |
74 |
- |
- |
- |
- |
- |
16 |
76 |
70 |
95 |
85 |
109 |
99 |
- |
- |
- |
- |
- |
25 |
100 |
91 |
126 |
111 |
143 |
130 |
158 |
140 |
183 |
163 |
138 |
35 |
125 |
111 |
156 |
138 |
176 |
161 |
195 |
176 |
226 |
203 |
171 |
50 |
149 |
135 |
189 |
168 |
228 |
209 |
293 |
215 |
274 |
246 |
209 |
70 |
189 |
170 |
240 |
214 |
293 |
268 |
308 |
279 |
351 |
318 |
270 |
95 |
228 |
205 |
290 |
259 |
355 |
326 |
375 |
341 |
426 |
389 |
330 |
120 |
263 |
235 |
336 |
299 |
413 |
379 |
436 |
398 |
495 |
453 |
385 |
150 |
300 |
270 |
375 |
328 |
476 |
436 |
505 |
461 |
570 |
524 |
445 |
185 |
341 |
306 |
426 |
370 |
545 |
500 |
579 |
530 |
651 |
600 |
511 |
240 |
400 |
358 |
500 |
433 |
644 |
590 |
686 |
630 |
769 |
711 |
606 |
300 |
459 |
410 |
573 |
493 |
743 |
681 |
794 |
730 |
886 |
824 |
701 |
Voltage Drop (Per Amp Per Meter)
Size of conductor |
2 cables d.c. |
2 cables, single-phase a.c. |
3 or 4 cables, 3-phase a.c. |
|||||||||||||
Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall) |
Ref. Methods 1 and 11 (clipped direct or on trays touching) |
Ref. Methods |